Fixing guides

When fixed mechanically Rockpanel boards must be assembled with Rockpanel fixings on a suitable subframe (aluminium rail support or timber frame) and free of tension. When determining the subframe the following should be kept in mind:

  • wind loading
  • the maximum fixing centres for the boards
  • the required ventilation provisions
  • unimpeded movement of the boards
  • legal local requirements

In the table below you will find the designloads for the strength of the fastener [N], the values are to both mechanical and non-mechanical fixing.





Panel thickness = 8 mm
ar1 = 15 mm
ar2 = 50 mm


Location of the fastening:

M = Middle of the panel
E = Edge of the panel
C = Panelcorner

 Max. distance c.t.c. (mm)Maximum designloads* (N)
BefestigungsmittelabMEC
Rockpanel Tack Sn.a.6001 N/mm11 N/mm11 N/mm1
Ring shank nail400600190190130
Screw60060033018085
Rivet600600435230115
* Designloads including a safety factor of 3